The 50A65 has only one serviceable part–an automotive
type fuse, which protects the low voltage transformer from
damage if its output is short-circuited. If the fuse has opened
up, remove whatever caused the short circuit and replace the
fuse with only a 3 Amp automotive type fuse. If the fuse is not
the cause of the control’s problem, replace the entire 50A65
control. There are no other user serviceable parts.
Additional jumper wires are included in this package and
should be used if the original wiring does not reach the
control after mounting. Refer to the furnace wiring diagram for
proper connection of the wires.
Some applications may require connection to terminal E33 lo-
cated in the middle of the contol cover. If the control being re-
placed does not have this connection, it is not needed in the
application and connection to terminal E33 is not required.
Trane application - Jumper wire 151-2906 (provided with
control) must be installed on the furnace from R01 to R02 of
the 12-pin connector.
Terminal
block with
captive
screws
12-pin
connector
& harness
4-pin
connector
& harness
spade terminal
spade terminal
spade terminal
spade terminal
spade terminal
spade terminal
spade terminal
spade terminal
spade terminal
spade terminal
spade terminal
spade terminal
3/16" spade terminal
50A65
TERMINAL
TERMINAL
TYPE
SYSTEM COMPONENT
CONNECTION
TYPICAL SYSTEM WIRING TABLE
* maximum recommended flame probe wire length is 36 inches.
W
G
R
Y
C
MV (2 terminals)
TR
TH
FP
PS
HLI
HLO
GND
(3 unused terminal)
IND
IGN
IND N
IGN N
COOL
HEAT
PARK (2 terminals)
LINE
XFMR
EAC (optional)
HUM (optional)
CIR N
LINE N
XFMR N
EAC N (optional)
HUM N (optional)
E33
low voltage thermostat W terminal (or equivalent)
low voltage thermostat G terminal (or equivalent)
low voltage thermostat R terminal (or equivalent)
low voltage thermostat Y terminal (or equivalent)
(2nd wire from Y terminal goes to 24 VAC HOT side of
compressor contactor coil)
24 VAC COMMON side of compressor contactor coil
gas valve (both gas solenoids are connected in parallel)
24 VAC transformer (low voltage COMMON side)
24 VAC transformer (low voltage HIGH side)
flame sensor probe*
pressure switch INPUT
high limit INPUT
high limit OUTPUT
MUST BE RELIABLY GROUNDED TO CHASSIS
inducer HOT side
ignitor HOT side
inducer NEUTRAL side
ignitor NEUTRAL side
circulator blower COOL SPEED terminal
circulator blower HEAT SPEED terminal
unused circulator blower terminals
input voltage (120 VAC) HOT side
24 VAC transformer line voltage HOT side
electronic air cleaner HOT side
humidifier HOT side
circulator blower NEUTRAL terminal
input voltage (120 VAC) NEUTRAL side
24 VAC transformer line voltage NEUTRAL side
electronic air cleaner NEUTRAL side
humidifier NEUTRAL side
Auxiliary flame sense
INTEGRATED
FURNACE CONTROLS
WIRING AND
CONFIGURATION
www.white-rodgers.com