REMOTE SENSOR
TROUBLESHOOTING REMOTE SENSORS
Note: The diagram below shows how to attach an isolation relay to
the “W” or “Y” circuit to provide constant power on power stealing
thermostats. This willl allow the thermostat to operate properly with
a remote sensor.
Figure 1 shows a single transformer heating/cooling system, with
isolation relays installed in the heating (W) and cooling (Y) circuits.
To simplify the diagram, limit and safety switches are not shown
here, although they will be found either in the low or high voltage
circuit. Limit and safety switches must be retained. Refer to the
equipment manufacturer’s system wiring diagram for the location of
limit and safety switches.
* Isolation Relay Wiring
Transformer
Red Jumper Wire
THERMOSTAT
24 VAC
Line
Voltage
Figure 1. Wiring for single transformer systems
RH W Y RC
Heating
System
Cooling
System
DO NOT REMOVE OR WIRE AROUND LIMIT AND
SAFETY SWITCHES WHEN INSTALLING ISOLA-
TION RELAYS.
WARNING
!
temperature is steadily dropping, reading low, or reads 08°, or displays – – – (3 dashes) when a remote sensor is installed,
it can be traced to one of the three following conditions.
Troubleshooting ChartTroubleshooting Chart
Troubleshooting ChartTroubleshooting Chart
Troubleshooting Chart
To function correctly and read temperature accurately, the thermostat must have constant 24-volt power. If the thermostat
ConditionCondition
ConditionCondition
Condition
TestTest
TestTest
Test
CommentsComments
CommentsComments
Comments
1. Loss of 24-volt power. On models with batteries, remove the batteries and re-install For the sensor to read correctly,
thermostat. If the display is blank, check heating and cooling the 24-volt system power
mustmust
mustmust
must
system to determine why 24-volt power is absent. be present. Some systems may
require an isolation relay* to
provide constant power to the
thermostat. Limit or safety
devices in the equipment can
also cause a power interruption.
2. A broken wire on S1, Disconnect sensor wires at thermostat. Attach a short piece Repair or replace the 3 wire
S2 and S3 or (+, SA, -) (2') of three-wire shielded cable to S1, S2 and S3 or (+, SA, shielded cable. Be sure the
from the thermostat to -) on the subbase. Bring the remote sensor to the thermostat remote wire run is not parallel
the remote. location and attach S1, S2 and S3 or (+, S, -) respectively. to line voltage wires that carry
Reattach thermostat. If the temperature begins to climb heavy inductive loads, or across
(slowly), it is reading correctly. If it reads correctly with the 2' fluorescent light ballasts that
length but improperly when attached to the wire run, it may cause an inductance to be
.tatsomreht eht ot dettimsnart.nur eriw eht ni tluaf a setacidni
3. A shorted or Because it is an electronic sensor, there are no Ohm values Replace remote sensor.
damaged remote sensor. to test. If correct conditions as
listed in 1 & 2 above and th
e
temperature stays at or near
08°08°
08°08°
08°, it indicates a shorted or
damaged remote sensor.
NoteNote
NoteNote
Note: Digital thermostats and remote sensors acclimate very slowly to temperature change. It may take an hour or more for
the temperature to acclimate to the room temperature from a low temperature reading as outlined above. To expedite the
room temperature display use the reset instructions listed in the installation instructions for the thermostat model you are
working with. When reset, the thermostat will default to a room temperature of 70° and begin sensing room temperature. Be
sure to reconfigure the installer menu for a remote sensor because the reset function may cancel remote sensing.
www.white-rodgers.com
166
TECHNICAL HELP