4) Select Energy Management Recovery OFF or ON
EnergyManagementRecovery(EMR)causesthethermostat
tostartheatingorcoolingearlytomakethebuildingtem-
peraturereachtheprogramsetpointatthetimeyouspecify.
Heatingwillstart5minutesearlyforevery1°oftemperature
required to reach setpoint. Cooling allows more time per
degreebecauseittakeslongertoreachtemperature.
Example:YouselectEMRandhaveyourheatingprogrammed
to65°atnightand70°at7AM.Ifthebuildingtemperature
is65°thedifferencebetween65°and70°is5°.Allowing5
minutesperdegreethethermostatsetpointwillchangeto
70°at6:35AM.
5) Select filter replacement run time -Thethermostatwill
display“FLTR” afterasettimeofoperation.Thisisareminder
tochangeorcleanyourairlter.Thistimecanbesetfrom
0to1950hoursin50hourincrements.A selection of 000
will cancel this feature.When“FLTR”isdisplayed,you
canclearitbypressingHOLDandRUNatthesametime.
Thisresetsthetimerandstartscountingthehoursuntilthe
nextlterchange.Changingthetimeinthemenualsoresets
thetimer.
6) Select Compressor Lockout LOC OFF or ON-Selecting
LOCONwillcausethethermostattowait5minutesbefore
turningonthecompressoriftheheatingandcoolingsystem
losespower.Itwillalsowait5minutesminimumbetween
coolingcycles.Thisisintendedtohelpprotectthecompres-
sorfromshortcycling.Somenewercompressorsalready
have a time delaybuiltinanddonotrequirethisfeature.
Yourcompressormanufacturercantellyouifthefeatureis
alreadypresentintheirsystem.Whenthecompressortime
delayoccursitwillashthe(snowakeicon)foraboutve
minutesthenturnonthecompressor.
7) Select Temperature Display Adjustment 4 LO to 4 HI-Al-
lowsyoutoadjusttheroomtemperaturedisplay4°higheror
lower.Yourthermostatwasaccuratelycalibratedatthefactory
butyouhavetheoptiontochangethedisplaytemperature
tomatchyourpreviousthermostat.
8) Select F° or C° Readout-Changesthedisplayreadoutto
CentigradeorFahrenheitasrequired.
OPERATING FEATURES
Nowthatyouarefamiliarwiththethermostatbuttonsanddisplay,
readthefollowinginformationtolearnaboutthemanyfeatures
ofthethermostat.
• SIMULTANEOUS HEATING/COOLING PROGRAM STOR-
AGE — When programming, you can enter both your
heatingandcoolingprogramsatthesametime.Thereis
noneedtoreprogramthethermostatatthebeginningof
eachseason.
• TEMPERATURE OVERRIDE—Press
or untilthe
displayshowsthetemperatureyouwant.Thethermostat
willoverridecurrentprogrammingandkeeptheroomtem-
peratureattheselectedtemperatureuntilthenextprogram
periodbegins.Thenthethermostatwillautomaticallyrevert
totheprogram.
• HOLD TEMPERATURE—Thethermostatcanholdany
temperaturewithinitsrangeforanindeniteperiodwithout
revertingtotheprogrammedtemperature.Momentarilypress
HOLDbutton.“HOLD”willbedisplayed.Thenchoosethe
desiredtemperaturebypressing
or .Thethermostat
willholdtheroomtemperatureattheselectedsettinguntil
youpressRUNbuttontostartprogramoperationagain.
• CONFIGURATION MENU — Allows you to customize
certainthermostatoptions.
PROGRAMMING YOUR THERMOSTAT
This section will help you plan your thermostat’s program to
meetyourneeds.Formaximumcomfortandefciency,keepthe
followingguidelinesinmindwhenplanningyourprogram.
• When heating (cooling) your building, program the
temperaturestobecooler(warmer)whenthebuildingis
vacantorduringperiodsoflowactivity.
• During early morning hours, the need for cooling is
usuallyminimal.
1
Step Press Button(s) Displayed (Factory Default) Press or to select: COMMENTS
HOLD
(0:00)
0 to 8 hrs (in
15 minute increments)
2
(FA)
SL
Select temporary Hold time
4
5
E
(ON)
OFF
6
7
LOC
(OFF)
ON
0 HI
(0)
4 LO to
4 HI
(F) C
Returns to normal operation
8
9
Select Energy Management Recovery OFF or ON
Select compressor lockout OFF or ON
Select temperature display adjustment higher or lower
Select temperature display to F or C
RUN
PRGM
and RUN
HOLD
*
HOLD
*
3
d-L
(ON)
OFF
Select display backlight OFF or ON
HOLD
*
HOLD
*
Filter
(000)
0 to 1950 hours
(in 50 hour increments)
Select filter replacement run time
HOLD
*
HOLD
*
HOLD
*
Select FA or SL (Fast or Slow) heating cycle rate
Configuration Menu
* Press
HOLD to advance to next item or TIME to move backwards to previous item