To prevent electrical shock and/or equipment damage
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause
shock or fire hazard.
Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will damage
thermostat and could cause personal injury and/or
property damage.
Printed in U.S.A.
DESCRIPTION
1F81-71
Programmable Electronic
Digital Automatic Changeover Multi-stage Thermostat
INSTALLATION AND
OPERATION INSTRUCTIONS
PART NO. 37-5938B
Replaces 37-5938A
9912
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
Your new White-Rodgers 5-Day/2-Day Digital Multi-stage Ther-
mostat uses the technology of a solid-state microcomputer to
provide precise time/temperature control. This thermostat offers
you the flexibility to design heating and cooling programs that fit
your needs.
Features:
Separate 5-day (weekday) and 2-day (weekend) programming
with four separate time/temperature periods per program
Simultaneous heat and cool program storage
Optional C terminal (dual power option)
Optional Energy Management Recovery (EMR)
PRECAUTIONS
SPECIFICATIONS
Optional B and O terminals
Preprogrammed temperature control
LCD continuously displays set point, and alternately dis-
plays time and room temperature
Temperature override until next program period
Manual program override (HOLD temperature)
°F/°C convertibility
Temperature range 45° to 90°F
Two-stage heat/two-stage cool
Armchair programming capability
This thermostat is intended for use with a 24-volt system; do not
use this thermostat with a millivolt or line voltage system. If in
doubt about whether your wiring is millivolt, line, or low voltage,
have it inspected by a qualified heating and air conditioning
contractor or electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and
ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.
ELECTRICAL DATA
Electrical Rating:
20 to 30 VAC 50/60 Hz. or D.C.
0.05 to 1.5 Amps (Load per terminal)
2.5 Amps Maximum Total Load (All terminals combined)
THERMAL DATA
Setpoint Temperature Range:
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature Range:
32°F to 105°F
Operating Humidity Range:
0 to 90% RH (non-condensing)
Shipping Temperature Range:
-40°F to 150°F
APPLICATIONS
For use with:
Heat/cool systems with up to two stages heat, two
stages cool
DO NOT USE WITH:
Millivolt systems
Systems exceeding 30 VAC and 2.5 amps
3-wire zoned hydronic heating systems
CAUTION
!
WARNING
!
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398
WHITE-RODGERS
Seitenansicht 0
1 2 3 4 5 6 7 8

Inhaltsverzeichnis

Seite 1 - WHITE-RODGERS

To prevent electrical shock and/or equipment damagedisconnect electric power to system at main fuse orcircuit breaker box until installation is comple

Seite 2 - INSTALLATION

2INSTALLATIONREMOVE OLD THERMOSTAT1. Shut off electricity at the main fuse box until installation iscomplete. Ensure that electrical power is disconne

Seite 3 - NOTE NOTE

3NOTE NOTEThe following wiring diagrams show typical terminal identifica-tion and wiring. For proper installation, refer to the originalmanufacturer&a

Seite 4 - Cooling System

4CHECK THERMOSTAT OPERATIONIf at any time during testing, your system does not operateproperly, contact a qualified serviceperson.Fan Operation1. Turn

Seite 5 - COOL-OFF-HEAT-AUTO

5OPERATIONBefore you begin programming your thermostat, you should befamiliar with its features and with the display and the location andoperation of

Seite 6 - PROGRAMMING YOUR THERMOSTAT

6• TEMPERATURE DISPLAY ADJUSTMENT — Your newthermostat has been accurately set in our factory. However,if you wish, you may adjust your new thermostat

Seite 7 - MO TU WE TH FR

7EXAMPLE: MO TU WE TH FRThis display window shows that for the 1st weekday period,the start time is 6:00 AM, and 70° is the programmedtemperature (thi