Seitenansicht 0
24A06G-1
DUAL LEVEL-TEMP
SILENT OPERATOR RELAY
(Normally Open Contacts)
INSTALLATION INSTRUCTIONS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
PRECAUTIONS
This Dual Level-Temp Silent Operator Relay is designed for con-
trolling two separate loads with a single low voltage thermostat.
It is especially suitable for use with electric heating equipment.
The Dual Level-Temp relay may be used to operate two separate
heating loads by means of a single low voltage thermostat. It
is equally well suited for use with a heating-cooling thermostat
to control heating and cooling loads alternately as in motels,
apartments, ofce buildings, etc.
This model Dual Level-Temp relay has a voltage input of 240
volts. Since this relay is equipped with a self-contained trans-
former, the supply voltage used must agree with the voltage
rating of the relay. This model has both an inductive and non-
inductive rating.
If in doubt about whether your wiring is millivolt, line, or low
voltage, have it inspected by a qualied heating and air con-
ditioning contractor, electrician, or someone familiar with basic
electricity and wiring.
Do not exceed the specication ratings.
All wiring must conform to local and national electrical codes
and ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.
DESCRIPTION
SPECIFICATIONS
ELECTRICAL DATA
Switch Action: Two SPST switches, normally open
Thermal: Average time delay – 45 seconds
Ambient Temperature: -20° to 120°F (-24° to 49°C)
Mounting: 1/2" conduit hub or two key slot mounting holes
Thermostat Circuit Current:
Bimetal Heater #1 (Red & White Leads) 0.21 Amps
Bimetal Heater #2 (Red & Black with White Stripe
Leads) – 0.21 Amps
The Silent Operator relay has been carefully adjusted at the fac-
tory, and no attempt should be made to adjust them in the eld.
CAUTION
!
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
WARNING
!
Do not use on circuits exceeding specied voltage.
Higher voltage will damage control and could cause
shock or re hazard.
PART NO. 37-4165D
Replaces 37-4165C
1236
www.white-rodgers.com
www.emersonclimate.com
TYPE
NUMBER
INPUT
VOLTAGE /FREQUENCY
ELECTRICAL RATING
FOR SWITCH #1
(Red and Black Leads)
FOR SWITCH #2
(Red Striped and Black Striped Leads)
NON-INDUCTIVE INDUCTIVE* NON-INDUCTIVE INDUCTIVE*
24A06G-1 240VAC, 60 Hz 25A, 6000W 12 FLA (72 LRA) 25A, 6000W 12 FLA (72 LRA)
*FLA - Full Load Amps.; LRA - Locked Rotor Amps.
Seitenansicht 0
1 2 3 4 5 6 7 8

Inhaltsverzeichnis

Seite 1 - 24A06G-1

24A06G-1DUAL LEVEL-TEMP SILENT OPERATOR RELAY (Normally Open Contacts)INSTALLATION INSTRUCTIONSOperator: Save these instructions for future use!FAILU

Seite 2 - WIRING AND OPERATION

2WR2-WIREHEATINGTHERMOSTATTYPE 24A06 DUAL LEVEL TEMPWHITEBLACKW/WHITESTRIPEREDBIMETALHEATER #1BIMETALHEATER #2SWITCH #1SWITCH #2TRANSFORMERHEATINGLOAD

Seite 3 - Line Voltage Low Voltage

3 WIRING AND OPERATION (cont.)All wiring should be done in accordance with local and national electrical codes and ordinances. WIRING Lin

Seite 4 - The Emerson logo is a

White-Rodgers is a business of Emerson Electric Co.The Emerson logo is a trademark and service mark of Emerson Electric Co.www.white-rodgers.comwww.e

Seite 5

www.white-rodgers.comwww.emersonclimate.comWhite-Rodgers est une affaire d’Emerson Electric Co.Le logo d’Emerson est une marque de commerce et une mar

Seite 6 - Basse tension

3 CÂBLAGE ET FONCTIONNEMENT (suite)Tout le câblage doit respecter les codes et règlements qui régissent les installations électriques. Fig. 3. Uti

Seite 7 - CÂBLAGE ET FONCTIONNEMENT

2INSTALLATION Le relais « Level-Temp » jumelé s’installe dans n’importe quelle position, sans que cela n’en détériore le rendement. On le raccorde à l

Seite 8 - TYPE 24A06G-1

DESCRIPTIONLe relais silencieux « Level-Temp » jumelé est conçu pour com-mander deux charges distinctes à l’aide d’un seul thermostat à basse tensi

Kommentare zu diesen Handbüchern

Keine Kommentare